(812) 309-78-59
(495) 223-46-76
ASTM E2484-08
Standard Specification for Multi-Story Building External Evacuation Controlled Descent Devices
16 стр.
Заменен
Печатное изданиеЭлектронный (pdf)
107.64 $ (включая НДС 20%)
Разработчик:
Зарубежные/ASTM
ICS:
13.340.60 Protection. Including safety ropes, harnesses and fall arrestors / Защита от падения и скольжения. Включая предохранительные тросы, ремни безопасности и страховочный ремень91.140.99 Other installations in buildings / Установки в зданиях прочие
Сборник (ASTM):
04.12 Building Constructions (II): E2112-latest; Sustainability; Asset Management; Technology and Underground Utilities / Строительство зданий (II): с E2112 и далее; Устойчивость; Система управления недвижимостью (системы эксплуатации зданий и сооружений); Технологии и Подземные коммуникации
Тематика:
Buildings
Описание
Реферат

This specification defines the material requirements, performance, design, marking instructions, test methods, ancillary components, requirements for the installation, periodic maintenance when installed, and instructions for the use of multi-story building external evacuation controlled descent device (CDD) systems for emergency escape of persons who cannot use the standard exit facilities in multi-story buildings. This specification does not apply to personal escape parachutes, ropes, chain ladders or rappelling devices. This specification does not apply as well to ancillary components used with and included in CDD systems, harnesses, connecting hardware, signage, special evacuation openings, personal protection equipment or devices and other components used on CDD systems which may be installed, purchased or used in accordance with the requirements specified herein.

Область применения

1.1 This specification covers the requirements, performance, design, marking instructions, test methods and ancillary components of Multi-Story Building External Evacuation Controlled Descent Device (CDD) systems for emergency escape of persons who cannot use the standard exit facilities in multi-story buildings, defines requirements for their installation, periodic maintenance when installed and instructions for their use.

1.2 This specification does not apply to personal escape parachutes, rope, chain ladders or rappelling devices.

1.3 This specification does not apply to ancillary components used with and included in CDD systems, harnesses, connecting hardware, signage, special evacuation openings, personal protection equipment or devices and other components used on CDD systems which may be installed, purchased or used in accordance with the requirements specified herein.

1.4 The values stated in SI units are to be regarded as the standard.

1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

Ключевые слова:
building evacuation; controlled descent device; emergency evacuation; external evacuation; high-rise; high-rise fires; multi-story building fire and rescue; multi-story buildings; rescue; Controlled descent device; Evacuation; External evacuation; High-rise building