(812) 309-78-59
(495) 223-46-76
ASTM E681-04
Standard Test Method for Concentration Limits of Flammability of Chemicals (Vapors and Gases)
12 стр.
Заменен
Электронный (pdf)Печатное издание
107.64 $ (включая НДС 20%)
Разработчик:
Зарубежные/ASTM
ICS:
13.300 Protection. Including performance requirements for dangerous goods, their handling, storage, transportation, marking, labelling, etc. / Защита от опасных грузов. Включая требования к рабочим характеристикам опасных грузов, их обработке, хранению, транспортированию, маркировке, этикетированию и т.д.
Сборник (ASTM):
14.05 Statistical Methods; Hazard Potential of Chemicals; Thermal Measurements; Manufacture of Pharmaceutical and Biopharmaceutical Products / Статистические методы; Потенциальная опасность химических веществ; Измерения теплопроводности; Производство фармацевтических изделий
Тематика:
Industrial Chemicals
Описание
Значение и использование

The LFL and UFL of gases and vapors define the range of flammable concentrations in air.

Limits of flammability may be used to determine guidelines for the safe handling of volatile chemicals. They are used particularly in assessing ventilation requirements for the handling of gases and vapors. NFPA 69provides guidance for the practical use of flammability limit data, including the appropriate safety margins to use.

Note 2—For hydrocarbons, the break point between nonflammability and flammability occurs over a narrow concentration range at the lower flammability limit, but the break point is less distinct at the upper limit. For materials found to be non-reproducible per 13.1.1 that are likely to have large quenching distances and may be difficult to ignite, such as ammonia and certain halogenated hydrocarbon, the lower and upper limits of these materials may both be less distinct. That is, a wider range exists between flammable and nonflammable concentrations (see Annex A1).

Note 3—This method measures the LFL and UFL for upward (and partially outward) flame propagation. the limits for downward flame propagation are narrower.

Область применения

1.1 This test method covers the determination of the lower and upper concentration limits of flammability of chemicals having sufficient vapor pressure to form flammable mixtures in air at atmospheric pressure at the test temperature. This test method may be used to determine these limits in the presence of inert dilution gases. No oxidant stronger than air should be used.

Note 1—The lower flammability limit and upper flammability limit are also referred to as the lower explosive limit (LEL) and the upper explosive limit (UEL), respectively.

1.2 This test method is based on electrical ignition and visual observations of flame propagation. Users may experience problems if the flames are difficult to observe (for example, irregular propagation or insufficient luminescence in the visible spectrum), if the test material requires large ignition energy, or if the material has large quenching distances.

1.3 provides a modified test method for materials (such as certain amines, halogenated materials, and the like) with large quenching distances which may be difficult to ignite.

1.4 In other situations where strong ignition sources (such as direct flame ignition) is considered credible, the use of a test method employing higher energy ignition source in a sufficiently large pressure chamber (analogous, for example, to the methods in Test Method E 2079 for measuring limiting oxygen concentration) may be more appropriate. In this case, expert advice may be necessary.

1.5 The flammability limits depend on the test temperature and pressure. This test method is limited to an initial pressure of the local ambient or less, with a practical lower pressure limit of approximately 13 kPa (100 mm Hg). The maximum practical operating temperature of this equipment is approximately 150°C (302°F).

1.6 The values stated in SI units are to be regarded as the standard. The values given in parentheses are provided for information only.

1.7 This test method should be used to measure and describe the properties of materials, products, or assemblies in response to heat and flame under controlled laboratory conditions and should not be used to describe or appraise the fire hazard or fire risk of materials, products, or assemblies under actual fire conditions. However, results of this test method may be used as elements of a fire risk assessment that takes into account all of the factors pertinent to an assessment of the fire hazard of a particular end use.

1.8 This standard may involve hazardous materials, operations, and equipment. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. Specific precautionary statements are given in Section 8.

Ключевые слова:
flammability; chemicals; vapors; gases