1.1 This specification covers the requirements for HFC-125 as a fire-fighting medium.
1.2 This specification does not address the fire-fighting equipment or hardware that employs HFC-125 or the conditions of employing such equipment, for example, hand helds, fixed installations, etc.
1.3 This specification does not address the storage or transportation of HFC-125. Storage, handling, and transportation issues are addressed in Practice D6268.
1.4 The following safety hazards caveat pertains to the test methods portion, Section 6, of this specification. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. Specific hazards statements are given in Note 1.