This European Standard specifies requirements, test methods and performance criteria for line smoke detectors
utilising the attenuation and/or changes in attenuation of an optical beam, for use in fire detection systems installed
in buildings.
This European Standard does not cover:
Line smoke detectors designed to operate with separations between opposed components of less than 1 m;
Line smoke detectors whose optical path length is defined or adjusted by an integral mechanical connection;
Line smoke detectors with special characteristics, which cannot be assessed by the test methods in this European
Standard.
NOTE The term "optical" is used to describe that part of the electromagnetic spectrum produced by the transmitter to which the
receiver is responsive; this is not restricted to visible wavelengths.
Diese Europäische Norm legt Anforderungen, Prüfverfahren und Leistungsmerkmale für linienförmige Rauchmelder
fest, die die Dämpfung und/oder die Änderungen der Dämpfung eines optischen Strahls in Brandmeldeanlagen in
Gebäuden auswerten.
Diese Europäische Norm behandelt nicht:
linienförmige Rauchmelder, die für den Betrieb zwischen gegenüberliegenden Bestandteilen mit einem
Abstand kleiner als 1 m ausgelegt sind;
linienförmige Rauchmelder, deren optische Messstrecke mit einer inneren mechanischen Verbindung
festgelegt wird oder einstellbar ist;
linienförmige Rauchmelder mit speziellen Kenngrößen, die durch die Prüfverfahren nach dieser Europäischen
Norm nicht bewertet werden können.
ANMERKUNG Der Begriff „optisch“ wird für den Bereich des elektromagnetischen Spektrums verwendet, der vom Sender
erzeugt wird und für den der Empfänger empfindlich ist; dieser Begriff ist nicht auf sichtbare Wellenlängen beschränkt.