OVE EN IEC 61869-10:2019-02

Действует
Instrument transformers - Part 10: Additional requirements for low-power passive current transformers (IEC 61869-10:2017) (english version)
This part of IEC 61869 is a product standard and covers only additional requirements for lowpower
passive current transformers. The product standard for low-power passive current
transformers comprises IEC 61869-1, together with IEC 61869-6 and this document with
specific requirements.
This document is applicable to newly manufactured low-power passive current transformers
with analogue output for use with electrical measuring instruments or electrical protective
devices having a rated frequency from 15 Hz to 100 Hz.
This document covers low-power passive current transformers used for measurement or
protection and multi-purpose low-power passive current transformers used for both
measurement and protection.
Subclause 5.6.1001 covers the accuracy requirements that are necessary for low-power
passive current transformers for use with electrical measuring instruments.
Subclause 5.6.1002 covers the accuracy requirements that are necessary for low-power
passive current transformers for use with electrical protective relays, and particularly for forms
of protection in which the prime requirement is to maintain the accuracy up to several times
the rated current. If required, the transient accuracy of low-power passive current
transformers during fault is also given in 5.6.1002.
Low-power passive current transformers have analogue voltage output only (for digital output
or for technology using any kind of active electronic components refer to IEC 61869-82). Such
low-power passive current transformers can include the secondary signal cable (transmitting
cable). The principle of operation of derivative low-power passive current transformers using
air-core coils (Rogowski coils) is given in Annex 10B and the principle of operation of
proportional low-power passive current transformers using iron-core coils with integrated
shunt is given in Annex 10C.
ICS