ÖVE/ÖNORM EN 60898-1:2013-03

Заменен
Electrical accessories - Circuit breakers for overcurrent protection for household and similar installations - Part 1: Circuit-breakers for a.c. operation (english version)
This part of IEC 60898 applies to a.c. air-break circuit-breakers for operation at 50 Hz or
60 Hz, having a rated voltage not exceeding 440 V (between phases), a rated current not
exceeding 125 A and a rated short-circuit capacity not exceeding 25 000 A.
As far as possible, it is in line with the requirements contained in IEC 60947-2.
These circuit-breakers are intended for the protection against overcurrents of wiring
installations of buildings and similar applications; they are designed for use by uninstructed
people and for not being maintained.
They are intended for use in an environment with pollution degree 2.
They are suitable for isolation.
Circuit-breakers of this standard, with exception of those rated 120 V or 120/240 V (see table 1),
are suitable for use in IT systems provided that the requirements of IEC 60364-4-473:1977 +
A1:1998 are complied with.
This standard also applies to circuit-breakers having more than one rated current, provided
that the means for changing from one discrete rating to another is not accessible in normal
service and that the rating cannot be changed without the use of a tool.
This standard does not apply to
– circuit-breakers intended to protect motors;
– circuit-breakers, the current setting of which is adjustable by means accessible to the user.
For circuit-breakers having a degree of protection higher than IP20 according to IEC 60529,
for use in locations where arduous environmental conditions prevail (e.g. excessive humidity,
heat or cold or deposition of dust) and in hazardous locations (e.g. where explosions are
liable to occur), special constructions may be required.
Requirements for circuit-breakers for a.c. and d.c. operation are given in IEC 60898-2.
Requirements for circuit-breakers which incorporate residual current tripping devices are to be
found in IEC 61009-1, IEC 61009-2-1, and IEC 61009-2-2.
A guide for co-ordination under short-circuit conditions between a circuit-breaker and another
short-circuit protective device (SCPDs) is given in annex D.
ICS
29.120.50 Fuses and other overcurrent protection devices / Плавкие предохранители и другие защитные устройства при перегрузках